4.2.4.4.3. DA (De-energize above setpoint)
Used in applications where failsafe control of an Overspeed
condition is desired. Operation is as follows:
If the monitored application is operating at a speed below
the setpoint, the relay is energized.
If the speed increases beyond the setpoint value, the
setpoint enters the alarm condition and de-energizes the
relay.
The relay will remain de-energized until the speed
decreases to a value below the reset point of the hysteresis
band at which point the relay is energized.
4.2.4.4.4. DB (De-energize below setpoint)
Used in applications where failsafe control of an
Underspeed condition is desired. Operation is as follows:
If the monitored application is operating at a speed above
the setpoint, the relay is energized.
If the speed decreases below the setpoint value, the setpoint
enters the alarm condition and de-energizes the relay.
The relay will remain de-energized until the speed
increases to a value above the reset point of the hysteresis
band at which point the relay is energized.
A, EB, DA, DB switching modes use both Fixed and Variable Range Constants